Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 137
C01.22 AI 1 gain N/A RWS 1 -16/16 PP V-F-S-B Full 5005
Analog Input 1 gain count value displaying.
How to perform the self-tuning procedure of the Analog input 1, if the input is -10V/
+10V (factory).
Tune Analog input 1 offset
C INTERFACE / C01 An Inp 1
Refer to 0 the position of the potentiometer connected to Analog input 1 terminals.
Enter the C01.18 - AI 1 offs tune parameter: "Start…" message will be displayed,
than press [Enter] key to run the procedure.
Wait up to "Autotune End" message will be displayed, than press three time
[Escape] key.
Tune Analog input 1 gain
C INTERFACE / C01 An Inp 1
Refer to maximum the position of the potentiometer connected to Analog input 1
terminals.
Enter the C01.19 - AI 1 gain tune parameter: "Start…" message will be displayed,
than press [Enter] key to run the procedure.
Wait up to "Autotune End" message will be displayed, than press three time
[Escape] key.