Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 138 ARTDrive V2 series - Instruction Manual
C02 INTERFACE / An Inp 2
See Analog Input 1 diagram and description details above.
C02.00 AI 2 sgn src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Full 5031
Ipa 4000 - NULL = Default
It connects the selected signal to the selector of the multiplier input: if the signal is 0,
multiply by +1, or if the signal is 1, multiply by -1. The multiplier allows to invert Analog
Input 2 signal.
ªª
ªª
ª
Pick List 3
C02.01 AI 2 alt sel src N/A RWS Ipa4000 PList 3 PIN V-F-S-B Full 5032
Ipa 4000 - NULL = Default
It connects the selected signal to the selector of the alternative reference for An. Inp. 2
block.
ªª
ªª
ª
Pick List 3
C02.10 AI 2 type N/A RWS 0 0/2 DP V-F-S-B Easy 5020
[0] -10V .. +10V As for “ AI 1 type” parameter description above
[1] 0.20mA,0.10V As for “ AI 1 type” parameter description above
[2] 4..20mA As for “ AI 1 type” parameter description above
NOTE! “An inp 2 type” selection requires a correct jumpers configuration of RV33
regulation card:
-10V...+10V & 0..10V S8=OFF – S9=OFF – S10=OFF
0..20mA & 4..20mA S8=ON – S9= ON – S10= ON
C02.11 AI 2 alt value [cnt] RWS 0 -32767/32767 PV V-F-S-B Full 5022
Alternative reference value in count for Analog input 2.
C02.12 AI 2 thr [%] RWS 20 -100/100 PP V-F-S-B Easy 5023
Analog Input 2 threshold value 100% is equal to 10V or 20mA.
C02.13 AI 2 scale N/A RWS 1 -16/16 PP V-F-S-B Easy 5024
Analog Input 2 scale factor.
C02.14 AI 2 offset [%] RWS 0 -100/100 PP V-F-S-B Full 5021
Analog Input 2 offset count value 100% is equal to 10V or 20mA.