REF&RAMP / Motopot
The Motopotentiometer function is enabled in the standard settings.
Furthermore, through the D09.00 - Mpot up src and D09.01 - Mpot down src sources it
is possible to select the origin of the Speed increase and decrease and of the command
signals. The Block offers also the possibility to invert the output reference. The D09.02 -
Mpot invers src source selects the inversion command. The speed preset source,
D09.03 - Mpot preset src, allows to select the preset command.
Such function can activate a series of settings active on the input and/or output
reference. In the Block configurations it is possible to set, with D09.10 - Mpot lower lim
and D09.11 - Mpot upper lim, the speed upper and lower limit (in rpm and standard
configured with 0 and 1500A (default for 230-480Vac), 1800A default for 575Vac).
The Motopotentiometer acceleration and deceleration ramps are independent from
those of the Ramp block.
This Block, therefore, with D09.12 - Mpot Acc Time and D09.13 - Mpot Dec Time, allows
to set the Motopotentiometer ramp.
D09.14 - Mpot init cfg allows to set the function stating the Motopotentiometer
reference value when the Drive is started.
Furthermore, D09.15 - Mpot preset cfg states the function of the Preset command.
+
Jog
_
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Mpot preset cfg
[0]None
Mpot init cfg
[1]Zero
Mpot upper lim
1800 rpm
Mpot lower lim
0 rpm
Mpot acc time
200 s
Mpot dec time
200 s
Mpot stop mode
[0]Last value
Mpot output
Mpot cmd mon
Mpot up src
NULL
Mpot down src
NULL
Mpot invers src
NULL
Mpot preset src
NULL
Figure D09: Motor potentiometer