MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 187
D09.14 Mpot init cfg N/A RWS 1 0/3 DP V-F-S-B Easy 7086
Motopot initial configuration:
[0] Power off Value at turning off
[1] Zero Zero rpm
[2] Lower limit Lower limit value
[3] Upper limit Upper limit value
D09.15 Mpot preset cfg N/A RWS 0 0/11 DP V-F-S-B Easy 7087
Motopot preset configuration:
[0] None No operation
[1] Inp = 0 The input state is set at zero
[2] Inp = low lim Low limit it sets on the input the Mpot lower limit
[3] Inp & Ref=0 It sets at zero the input and reference state
[4] Inp & Ref=low It sets on the input and on the reference the Mpot lower limit
[5] Out=0 It sets at zero the output state
[6] Out = lowlim It sets on the output the Mpot lower limit
[7] Out & Ref=0 It sets at zero the output and reference state
[8] Out & Ref=low It sets on the output and on the reference the Mpot lower limit
[9] Inp = upp lim It sets on the input the Mpot upper limit
[10] Inp&Ref=upp It sets on the input and on the reference the Mpot upper limit
[11] Freeze input It freezes the input reference independently of the following variations
D09.16 Mpot Stop mode N/A RWS 0 0/1 DP V-F-S-B Easy 7101
Behavior of the Motorpotentiometer reference after a Stop command:
[0] Last value Motorpotentiometer reference remains fixed to its current value.
[1] Follow ramp Motorpotentiometer reference ramps down to zero. When a Stop command is
given, motorpotentiometer reference follows the deceleration ramp in use.
D09.20 Mpot cmd mon N/A R 0 0/15 DP V-F-S-B Full 7089
It displays Motopot command activated.
D09.21 Mpot output [rpm] R 0.00 0.00/0.00 PV V-F-S-B Easy 7090
It displays Motopot block output signal.