Index
MENUMENU
MENUMENU
MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 294 ARTDrive V2 series - Instruction Manual
O03.13 PI steady delay [sec] RWS 1.00 Calc/Calc PP V-F-S-B Full 7263
Period of time, during which the P and I init gain gains are kept active after the PI steady
thr threshold has been overcome by the PID FF mon reference.
O03.14 PI steady thr [%] RWS 0.00 0.00/200 PP V-F-S-B Full 7264
Steady State detecting threshold value.
O03.15 PI P1 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7270
Proportional gain segment 1 value
O03.16 PI I1 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7271
Integral gain segment 1 value.
O03.17 PI P2 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7272
Proportional gain segment 2 value.
O03.18 PI I2 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7273
Integral gain segment 2 value.
O03.19 PI P3 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7274
Proportional gain segment 3 value.
O03.20 PI I3 gain % [%] RWS 10 0.00/100 PP V-F-S-B Full 7275
Integral gain segment 3 value.
O03.21 PIGP tran21 hthr [%] RWS 0.00 0.00/100 PP V-F-S-B Full 7276
Transition point value from segment 1 to segment 2.
O03.22 PIGP tran32 lthr [%] RWS 0.00 0.00/100 PP V-F-S-B Full 7277
Transition point value from segment 2 to segment 3.
O03.23 PIGP tran21 band [%] RWS 5 0.00/100 PP V-F-S-B Full 7278
Width of the transition band from 1 to 2.
O03.24 PIGP tran32 band [%] RWS 5 0.00/100 PP V-F-S-B Full 7279
Width of the transition band from 2 to 3.