EasyManuals Logo

GW Instek PSU Series Programming Manual

GW Instek PSU Series
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #93 background imageLoading...
Page #93 background image
REMOTE CONTROL
93
Return parameter
<NR1>
0~32767
:STATus:QUEStionable:INSTrument:
ISUMmary<n>:ENABle
Set
Query
Description
Sets or queries the bit sum of the Questionable
Instrument Summary Status Enable register.
(Multi-Drop mode).
Syntax
:STATus:QUEStionable:INSTrument:ISUMmary
<n>:ENABle <NR1>
Query Syntax
:STATus:QUEStionable:INSTrument:ISUMmary
<n>:ENABle?
Parameter
<n>
1,2 or 3
<NR1>
0~32767
Return parameter
<NR1>
0~32767
:STATus:PRESet
Set
Description
This command resets the ENABle register, the
PTRansistion filter and NTRansistion filter on the
Operation Status and Questionable Status
Registers. The registers/filters will be reset to a
default value.
Default Register/Filter Values
Setting
QUEStionable Status Enable
0x0000
QUEStionable Status Positive Transition
0x7FFF
QUEStionable Status Negative Transition
0x0000
QUEStionable Instrument Summary1
Status Enable
0x7FFF
QUEStionable Instrument Summary2
Status Enable
0x7FFF
QUEStionable Instrument Summary3
Status Enable
0x7FFF

Table of Contents

Other manuals for GW Instek PSU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GW Instek PSU Series and is the answer not in the manual?

GW Instek PSU Series Specifications

General IconGeneral
BrandGW Instek
ModelPSU Series
CategoryPower Supply
LanguageEnglish

Related product manuals