EasyManua.ls Logo

Haefely AXOS - Telecom Wave Test Transition Settings; Telecom Wave Test Trigger Settings

Haefely AXOS
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
Telecom Wave (Axos8 only)
Position
Description
External (Pin11 on Aux)
External condition (e.g. device or PLC signal), the position becomes 1
and causes an action (Ignore, Alarm, Test Stop or test stop & line off)
Line Current
Limits the current (L, N, PE front view) to the EUT.
Action: Ignore, Alarm, Test stop,
Test stop & line off
Due to EUT fails, AXOS
8
cause an action which can be: Ignore,
Alarm, Test Stop, Test Stop & Line off.
Turn Line off
Voltage locked at L, N, PE when test has finished
Sound
Acoustic signal when test ends
10.1.7 Transition
The Figure 9-10 reflects the transition window of the AXOS
8
. The “alternative polarity” makes
possible to switch between positive and negative impulses. Alternate polarity, peak voltage can
be selected and parameter entered.
Figure 10-10: Telecom Wave transition mode
After successfully entering the parameter, “OK” button can be pushed and then the “Start” button
in the main menu. Test should be proceeding now.
10.1.8 Trigger
In the trigger window it is possible to select between auto” or manual”. When being in “manual
modethe user controls the trigger by pressing the start button first, after the generator is charged
the menu button “trigger” flashes up and can be pushed. “Auto mode” provides the signal
according to set up and works completely automatically. All key parameter like “peak voltage”
sets the user through the touch screen in the main operating window.

Table of Contents