EasyManua.ls Logo

Haefely AXOS - Voltage Dips Test Properties; Voltage Dips Test Transition Settings

Haefely AXOS
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66
Voltage dips & interrupts
Figure 12-6: External transformer
Now the incoming V dip can be regulated directly at the transformer. Note: No further connection
of the link data cable at the rear view possible.
12.3.3 Properties
Position
Description
External (Pin11 on Aux)
External condition (e.g. device or PLC
signal), the position becomes 1 and causes
an action (Ignore,
Alarm, Test Stop or test stop & line off)
Line Current
Limits the current (L, N, PE front view) to the EUT.
Action: Ignore, Alarm, Test stop, Test stop &
line off
Due to EUT fails, AXOS
8
cause an action
which can be: Ignore, Alarm, Test Stop, Test
Stop & Line off.
Line off
Voltage locked at L, N, PE when test has finished
Sound on or off
Acoustic signal when test ends
12.3.4 Transition
The Figure 12-7: Voltage Dips Transition shows the transition” menu. It is possible to select
independently “Duration”, “Interval”, “Phase” and “Alternate polarity”. To be able to select “phase”
the Synchrony has to be either set as Synchronization or external Synchronization, otherwise it
is not possible to access it. Eventually, every parameter can be changed by pushing the certain
value.

Table of Contents