EasyManua.ls Logo

Hakko Electronics Monitouch V7 - Page 182

Hakko Electronics Monitouch V7
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
1. Ethernet 4-31
Network Communications
Read Words from Internal Memory
int HKEtn_ReadInternalMemory(WORD *dp,unsigned short Wordcnt,int
DeviceType,DWORD addr,char *lpAddr,int DFlag=1)
This function is retained until data is transferred from the V7 series.
Parameters
*dp Target block pointer
Wordcnt Word count to be transferred (max. 2000 words)
DeviceType 0: $u 1: $s
addr Top memory address to be read
*lpAddr IP address shown as a string of characters separated by dots
Example: “192.168.XXX.XXX”
DFlag 0, 1, 2 (Refer to page 4-29.)
Return values
Success TRUE
Failure FALSE
Error details Get using HKEtn_GetLastError ().
Contents Word Count
No. 1 1
No. 2 1
No. n 1

Table of Contents