5-78 11. Allen-Bradley PLC
SLC500 Series, Micro Logix 100:
Transmission Parameter Setting
CPU Port Channel 0
Set up the parameters for CPU port channel 0 using the software specifically designed for
this purpose.
1747-KE
Set up the parameters for 1747-KE using the software specifically designed for this
purpose.
Baud Rate : 19200
Duplicate Detect : ON
ACK Timeout (x 20 ms) : 20
Control Line : No Handshaking
Parity : EVEN
Error Detection : BCC
NAK Retries : 3
ENQ Retries : 3
Embedded Responses : AUTO-DETECT
DF1 Port Setup Menu
Baudrate : 19200
Bits Per Character : 8
Parity : Even
Stop Bits : 1
DF1 Full-Duplex Setup Parameters
Duplicate Packet Detection : Enabled
Checksum : BCC
Constant Carrier Detect : Disabled
Message Timeout : 400
Hardware Handshaking : Disabled
Embedded Response Detect : Auto Detect
ACK Timeout (× 5 ms) : 90
ENQuiry Retries : 3
NAK Received Retries : 3