EasyManuals Logo

Hitachi RPI-4.0FSN4E Service Manual

Hitachi RPI-4.0FSN4E
429 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #240 background imageLoading...
Page #240 background image
6 Optional functions
228
SMGB0077 rev.0 - 01/2013
Element Optional function
Individual
setting
Settings Condition setting Description
EA
Not available O
00
Not available
Use at 00 conditions
01
Eb
Fan operation control at
cooling Thermo-OFF
O
00
Not activated
function
This function reduces the unit fan
speed to reduce the spreading of
smells and humidity.
01 Low
02 Slow
EC
Forced Thermo-ON stoppage
at cooling
O
00
Not activated
function
This function is used to force stoppage
when cooling is complete.
01 Available
Ed
Not available O
00
Not available
Use at 00 conditions
01
EE
Automatic fan speed control O
00
Not activated
function
This function limits the unit operation
by automatically controlling the fan
speed when the room temperature is
close to the set temperature.
01 Activated function
F1
PC-ARF: Automatic OFF timer
setting
X
00
Not activated
function
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
Do not set the functions “0C”-”0F”
when two remote control switches
are used in the same remote control
group.
01 1 h
02 2 h
03 3 h
04-24 (04-24) h
0A 30 min
0B 90 min
PC-ART: Not available 00-0B Not available
F2
Remote control main-sub
setting
X
00 Main
This function is used when two remote
controls are installed in a system.
01 Sub
F3
PC-ARF: Automatic reset of
setting temperature
(4)
X
00
Not activated
function
This function releases the xed
temperature setting after a certain
time to limit unit operations and save
energy.
01 Activated function
PC-ART: Not available 00-01 Not available
F4
PC-ARF: Automatic reset time X
00
30 minutes (factory
setting)
This function is used to set the
automatic reset time with the
temperature setting
01 15 minutes
02 60 minutes
03 90 minutes
PC-ART: Not available 00-03 Not available

Table of Contents

Other manuals for Hitachi RPI-4.0FSN4E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RPI-4.0FSN4E and is the answer not in the manual?

Hitachi RPI-4.0FSN4E Specifications

General IconGeneral
BrandHitachi
ModelRPI-4.0FSN4E
CategoryAir Conditioner
LanguageEnglish

Related product manuals