105 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
System
Options
Communication
Options
Auto Time Test
Set the Hour
*02:00AM
Section
Set the Minutes
Select AM/PM
Enter Interval
24 hrs, 12 hrs,
*6 hrs, 4 hrs
Phone Lines
For each phone line (1 & 2) select:
Dialing Prefix Up to 9 digits *none
See “Phone Lines”
on page 125.
# of Answer Rings Range: 00-15 *06
Number of rings
before panel
answers a call
from a computer
See “Phone Lines”
on page 125.
Select Dialing Option
TT
*TT
Touch Tone
TT/PL
TouchTone
alternating with
pulse see See
“Phone Lines” on
page 125.
PULSE Pulse dialing
Rotary Pulse Format
U = 60/40
*U
See “Phone Lines”
on page 125.
E = 66/34
Dial Tone Disabled Y or N *N
Monitor Line Y or N *N
Answering Machine
Bypass
Y or N *N
Phone Line Unused Y or N *N
Edit Ethernet
IP Address
See “Edit
Ethernet” on
page 127.
Subn Mask
SubNet
Default Gateway
DHCP Enable