IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017 62
2. Use the 6-pin cable included with SK-NIC to connect the IFP-300/ECS to the SK-NIC. Connect the SK-NIC to the pin connector on
the control panel labeled Data Network. See Figure 5.6.
Figure 5.6 Panel to SK-NIC connection
3. Each SK-NIC has the ability to monitor for earth ground faults on the twisted pairs connected to Port 1 of its terminal block TB2.
Earth fault detection for any wiring at Port 2 of TB2 is done at the next/previous SK-NIC due to these wiring connections being
connected to Port 1 of TB2 at the next/previous SK-NIC.
4. Unused optic ports on fiber loop modules must have their dust caps placed on the port.
5. Based on the type of data medium chosen, run the twisted pair wiring/fiber optic cable to the next SK-NIC using a class B or class
A wiring method. A combination of both medium types can be used. See Figure 5.7, Figure 5.8, Figure 5.9, and Figure 5.10 for SK-
NIC wiring examples.
To mount the SK-NIC remotely:
Follow the steps above except, the 6-pin cable that runs from the SK-NIC to the IFP-300 must be run in conduit. See Figure 5.1.