Item Values Description
Generator Usage No Generator;
Generator In Use
The default value is No
Generator. Set the
parameter based on
site requirements.
Line Priority Line 1-Switch I; Line 2-
Switch II; No Line
Priority
The default value is
Line 1-Switch I. Set the
parameter based on
site requirements.
On the main menu screen, select device conguration and press . On
the device
conguration screen, you can set thresholds for parameters.
The following table lists the device conguration attributes and values.
Table 5-2 Device conguration attributes and values
Item Values Description
Voltage
Thresholds
Volt Threshold
Min LN1
–30% to –5% The step increase
is ±1%. The
default settings
are –10% for
LN1 and LN2.
Volt Threshold
Min LN2
–30% to –5%
Volt Threshold
Max LN1
+5% to +30% The step increase
is ±1%. The
default settings
are +10% for
LN1 and LN2.
Volt Threshold
Max LN2
+5% to +30%
Frequency
Thresholds
Freq Threshold
Min LN1
–10% to –1% The step increase
is ±1%. The
default settings
are –5% for LN1
and LN2.
Freq Threshold
Min LN2
–10% to –1%
Freq Threshold
Max LN1
+1% to +10% The step increase
is ±1%. The
default settings
are +5% for LN1
and LN2.
Freq Threshold
Max LN2
+1% to +10%
Modbus Modbus
Address
Local/Remote
There is no need
to reset the
parameter.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 132