Table 5-21 Power distribution settings for a power distribution unit
Path Parameter Name Default
Value
Description
Monitoring >
Power
Distribution >
General Input
Unit1 > Power
Distribution Unit
> Running
Parameters >
Unhide All
Advanced Signals
> Power
Distribution
Settings
QF1 Rated current (L1)
QF2 Rated current (L2)
NOTE
This parameter is not displayed for
some distribution units.
32 Rated current 32 A for
each branch.
QF1 Branch circuit breaker in use
(L1)
QF2 Branch circuit breaker in use
(L2)
Enable When the parameter is set
to Disable for a branch, all
alarms of the branch will
not be reported.
When the parameter is set
to Enable for a branch, all
alarms of the branch will
be reported.
Upper load current threshold 80 When the load current
exceeds the preset value,
an alarm is generated.
Lower load current threshold 60 When the load current is
lower than the preset
value, an alarm is
generated.
4. Set the parameters for other power distribution units in the same way or by
synchronizing parameters.
Path: Maintenance > Parameter Sync
Step 3 Go to the FusionModule2000 view, click Modify Device, select any general input
unit or power distribution unit, and click Automatic
identication.
You can set Power supply branch to manually change the link relationship.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning