Table 5-48 Management system parameters
Path Parameter Default
Value
Setting
System
Settings >
NMS
Application
> NetEco >
Communicat
ion
Parameters
Server IP 192.168.8.
11
IP address of the primary
management system server
NOTE
The management system IP address
and the ECC800-Pro IP address must be
congured in the same network to
ensure normal connection between the
management system and the ECC800-
Pro.
Standby
server IP
NOTE
This
parameter is
displayed
when Enable
standby
server IP
next to
Server IP is
selected.
192.168.0.
1
Set this parameter to the IP address
of the backup management system
server.
Port number 31220 31220
Network port
for link setup
WAN_1 ● WAN_1: Connects to the
management system over the
WAN1 port.
● WAN_2: Connects to the
management system over the
WAN2 port.
● WAN_1/WAN_2: Both the WAN1
and WAN2 ports are connected
to the management system. The
WAN1 or WAN2 port is
automatically selected based on
the real-time network
connection.
NOTE
If this parameter is set to WAN_1/
WAN_2, the IP address for
connecting to the management
system is not
xed. Therefore, the IP
address is displayed as 0.0.0.0,
indicating auto adaptation.
FusionModule2000-S Smart Modular Data Center