Maintenance
Item Method
Expected Result
Troubleshooting
Visual
inspection
The air lter is not
damaged or
distorted.
Replace the air
lter.
Compressor Visual
inspection
The compressor is
secured.
Tighten screws if
the compressor is
not secured.
Visual
inspection
The compressor
service valve has no
oil stains.
Clean up the oil
stains.
Listen to the
compressor
operating
sound.
The compressor
does not generate
abnormal sound
during operation.
Replace the
compressor.
Pipe connection Visual
inspection
The refrigerant pipe
does not leak or
corrode, and is
properly wrapped
with thermal
insulation foam.
Repair the leakage
points and rewrap
thermal insulation
foam.
Visual
inspection
The refrigerant pipe
support is secure
and intact.
Replace the support
and secure it again.
Indoor fan Visual
inspection
The indoor fan
guard is not
misshapen.
Repair or replace
the fan guard.
Visual
inspection
The indoor fan
blades are intact.
Replace the fan
assembly.
Check the
running
sound of the
indoor fan.
The operating
indoor fan
generates no
abnormal noise.
Replace the fan
assembly.
Visual
inspection
The screws on the
indoor fan are not
loose or distorted.
Tighten loose
screws.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 282

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals