EasyManuals Logo

Huawei FusionModule2000-S User Manual

Huawei FusionModule2000-S
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #295 background imageLoading...
Page #295 background image
Table 6-6 Quarterly maintenance for the cooling system
Maintenance
Item Method
Expected Result
Troubleshooting
Monitoring Export smart
cooling
product logs,
alarms,
temperature,
humidity, and
the operating
status and
time of the
compressor,
fan, electric
heater,
humidier,
and water
pump from
the
monitoring
system. View
the historical
alarms
generated and
select the
most common
ve ones. (If
no monitoring
system is
available, skip
this item.)
There are no
abnormal records in
alarms.
Locate the fault or
contact technical
support.
Electric heater Start the
equipment,
choose Maint
> Diagnostic
Mode > Enter
on the main
screen, and
start the
electric heater.
NOTE
To avoid burns,
do not touch
the electric
heater surface
with bare skin.
The electric heater
generates heat.
Replace the electric
heater.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 284

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals