Maintenance
Item Method
Expected Result
Troubleshooting
Wet lm
humidier
Start the
equipment,
choose Maint
> Diagnostic
Mode > Enter
on the main
screen, and
start the wet
lm
humidier.
Water drainage is
normal.
If no water is
supplied, check
the cable
connection or
replace the water
inlet solenoid
valve.
If no water is
supplied to the
wet
lm
humidier,
check
the cable
connection to the
water pump or
replace the
humidier water
pump.
Table 6-7 Quarterly maintenance for the management system
Maintenance
Item
Method Expected Result Troubleshooting
Battery
management
parameter
settings
On the UPS
LCD, choose
System Info >
Settings >
Battery
Param. and
check whether
battery
management
parameters
are set as
required.
The parameters are
set based on
requirements.
Set parameters
correctly.
Fire control
linkage function
Simulate a
smoky
environment
under the
smoke
detector. (If
real smoke is
not allowed,
press the TEST
button on the
sensor.)
A smoke alarm is
displayed on the
active alarm page of
the WebUI.
Check whether the
smoke detector is
faulty.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 285