5.3.13.1 NetEco6000 Management
5.3.13.1.1 Connecting a Communications Cable
Procedure
Step 1 Connect the communications cable to the WAN1 port on the ECC800-Pro.
Figure 5-50 Connecting the communications cable
----End
5.3.13.1.2 Setting NetEco Parameters
When the smart module can be connected to the NetEco, perform the following
steps to
congure parameters.
Procedure
Step 1 Apply for a xed IP address to the equipment room network administrator.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 5-23 IP parameters
Path
Parameter Default
Value
Setting
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
IP address 192.168.8.1
0
Set this parameter based on the IP
address assigned by the network
administrator.
Subnet
mask
255.255.25
5.0
Set this parameter based on the
subnet mask assigned by the network
administrator.
Default
gateway
192.168.8.1 Set this parameter based on the
default gateway address assigned by
the network administrator.
Step 3 Click Submit.
Step 4 Set the NetEco communication parameters and authentication password on the
ECC800-Pro WebUI.
FusionModule500 Smart Mini Data Center
User Manual 5 Power-On Commissioning