Page #295 background image
Figure 6-25 Detector position
(1) Smoke detector
Procedure
Step 1 Remove the smoke detector from the base.
Step 2 Remove the cables from the smoke detector and apply insulation measures such
as wrapping the cables with insulation tape to avoid hazards.
Step 3 Install the new smoke detector and reconnect the cables to the new smoke
detector.
Step 4 Install the smoke detector on the base.
Step 5 Blow smoke toward the smoke detector using a smoke pistol until the smoke
detector indicator changes from blinking once every 6s to steady on. If a smoke
detector
re alarm is triggered, the smoke detector is functional.
----End
6.4.3.11 Replacing a WLDS900 Water Sensor and Water Detection Rope
Prerequisites
Recommended tools and materials: Phillips screwdriver, crimping tool
A water sensor needs to be replaced.
A spare water sensor of the same model is available and functional.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 285

Table of Contents

Other manuals for Huawei FusionModule500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 and is the answer not in the manual?

Huawei FusionModule500 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500
CategoryStorage
LanguageEnglish

Related product manuals