Item Split-Type Air Conditioner
Indoor unit operating
humidity
5%–95% RH (non-condensing)
Storage temperature –40°C to +70°C (without refrigerant)
–40°C to +55°C (with refrigerant)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m (derated when the altitude ranges
from 1000 m to 4000 m)
Installation Requirements
Table 3-7 Installation requirements
Item Split-Type Air Conditioner
Installation mode Rack-mounted
Height distance between
indoor and outdoor units
–5 m to +20 m (outdoor unit placed higher)
Maximum equivalent length of
the one-way pipe
60 m. If the length exceeds 60 m, contact the
local customer service center.
3.3.2 Technical Specications
Table 3-8 Technical specications
Item
Split-Type Air Conditioner
Power system 220–240 V AC, 50 Hz, 1 phase
Refrigerant R410A
Cooling capacity
3.5 kW
a
Fan type EC fan
Air supply mode Front air supply and rear air return
Dimensions (H x W x D)
b
223 mm x 442 mm x 800 mm
Weight Indoor unit: < 40 kg
Outdoor unit: < 50 kg
IP rating Indoor unit: IP20
Outdoor unit: IPX5
FusionModule500 Smart Mini Data Center
User Manual 3 System Architecture
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 26