Figure 4-8 Leveling a cabinet
----End
4.2.4 Installing a Smart Cooling Product
4.2.4.1 Materials
(Optional) Refrigerant R410A
NO TICE
Do not use unqualied refrigerant. Huawei will not be liable for any equipment
damage caused by unqualied refrigerant.
Customers can purchase this material from Huawei or other vendors. Verify that
the refrigerant is authentic in the following ways:
1. Refrigerant from name brands such as DuPont, Daikin, and Honeywell is
recommended.
2. Dial the refrigerant vendor's hotline to
conrm the refrigerant authenticity.
3. Place the refrigerant tank indoors for 24 hours. Use a point thermometer to
measure the outer surface temperature of the refrigerant tank, and connect a
pressure gauge to the tank to measure the internal pressure, as shown in
FusionModule500 Smart Mini Data Center