Step 2 Remove the cables from the T/H sensor.
NO TICE
After removing cables, wrap exposed terminals with insulation tape and do not
block cable labels. If cable labels are blocked, cables may be connected incorrectly
later.
Step 3 Remove the faulty T/H sensor.
Step 4 Attach the new T/H sensor to an appropriate position on the cabinet door frame
based on the site requirements.
Step 5 Reinstall the cable removed from the T/H sensor.
NO TE
Before removing a T/H sensor, remember the DIP switch setting on it. When you install a
new T/H sensor, you need to set the same DIP switch setting for the new one.
----End
6.4.3.10 Replacing a Smoke Detector
Prerequisites
Recommended tools and materials: Phillips screwdriver, insulation tape, step
ladder (2 m)
A smoke detector needs to be replaced.
A spare smoke detector of the same model is available and functional.
Context
The smoke detector is installed on the top of the cabinet, as shown by (1) in
Figure 6-25.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 284

Table of Contents

Other manuals for Huawei FusionModule500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 and is the answer not in the manual?

Huawei FusionModule500 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500
CategoryStorage
LanguageEnglish

Related product manuals