Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Intelligent lithium
battery
monitoring system
Battery
management
alarm
- No battery
management
alarm is
generated.
Identify the
cause of an
alarm based on
the alarm
information.
Cleanliness - Wipe the battery
surface using a
piece of white
paper and the
paper does not
turn black.
Remove dust.
Battery
connection
- Battery terminals
and cables are in
good contact.
Locate poor
contact points
between battery
terminals and
cables.
Measurement of
the ambient
temperature of
the intelligent
battery
monitoring system
- The ambient
temperature of
the intelligent
battery
monitoring
system is lower
than 45°C.
Locate the
cause of an
abnormal
temperature.
Water sensor and
water detection
cable
Functions of the
water sensor and
water detection
cable
Place the water
detection cable
into the water
and check
whether a water
leakage alarm is
generated by the
water sensor.
A water leakage
alarm is
generated.
If a water
leakage alarm is
not generated,
replace the
water detection
cable.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 239

Table of Contents

Other manuals for Huawei FusionModule500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 and is the answer not in the manual?

Huawei FusionModule500 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500
CategoryStorage
LanguageEnglish

Related product manuals