Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
Shallow discharge
test
(recommended)
- Conduct a
shallow
discharge test
when the UPS is
backed up to
verify that the
batteries can
discharge
properly.
1. Locate the
cause when
an exception
is identied.
2. If the fault
persists,
contact
Huawei
technical
support.
ECC800-Pro AC input - Input voltage:
200–240 V AC
Frequency: 45–
55 Hz
If the input
voltage is
abnormal, check
the power grid
status and input
cable
connection.
Output voltage - Output voltage:
53.5 V DC±5%
If the output
voltage is
abnormal, check
the load power
and cable
connection.
Indicator - The indicator on
the power
module is steady
green.
Check the
output voltage
and determine
whether the
power module
is faulty. If the
power module
is faulty, replace
it.
Fan - No abnormal
noise is
generated.
If abnormal
noise is
generated, clean
the fan.
Operating
environment
- Ambient
temperature:
–20°C to
+65°C
Humidity:
0%–95% RH
(non-
condensing)
If the
temperature or
humidity is
abnormal, check
the smart
cooling product
status.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 244

Table of Contents

Other manuals for Huawei FusionModule500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 and is the answer not in the manual?

Huawei FusionModule500 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500
CategoryStorage
LanguageEnglish

Related product manuals