Maintenance
Area
Maintenance
Item
Operation Expected Result Troubleshootin
g
ECC800-Pro AC input - Input voltage:
200–240 V AC
Frequency: 45–
55 Hz
If the input
voltage is
abnormal, check
the power grid
status and input
cable
connection.
Output voltage - Output voltage:
53.5 V DC±5%
If the output
voltage is
abnormal, check
the load power
and cable
connection.
Indicator - The indicator on
the power
module is steady
green.
Check the
output voltage
and determine
whether the
power module
is faulty. If the
power module
is faulty, replace
it.
Fan - No abnormal
noise is
generated.
If abnormal
noise is
generated, clean
the fan.
Operating
environment
- ● Ambient
temperature:
–20°C to
+65°C
● Humidity:
0%–95% RH
(non-
condensing)
If the
temperature or
humidity is
abnormal, check
the smart
cooling product
status.
Monitoring
module indicator
- The monitoring
module indicator
is steady green
or blinking
green.
If the indicator
is o or any
abnormal
condition
occurs, see 6.2.2
Management
System
Troubleshootin
g to rectify the
fault.