Component Alarm Name Alarm
Severit
y
Possible Cause Measures
Inverter fault Critical The inverter output
short-circuits.
Eliminate the short
circuit at the output
port cable connection,
and then power on and
start the inverter again.
If the fault persists,
contact Huawei
technical support.
Output short
circuit
NOTE
The system
immediately
disconnects the
power output.
Critical The load or cable is
short-circuited.
Locate and rectify the
short circuit.
Intelligent
lithium
battery
monitoring
system
Communication
Failure
Critical The network cable
communication is
interrupted.
Check the cable
connection to the smart
ETH gateway.
BCB Tripping Critical The battery has
discharged to the
end-of-discharge
(EOD) threshold.
The battery circuit
breaker (BCB) box is
manually
disconnected.
There is a security
risk in the battery
loop.
Identify the alarm
cause, rectify the fault,
and switch on the BCB
box.
Single Batt.
terminal o
Critical A battery terminal
screw is not
tightened.
The battery terminal
is not properly
connected to the
connector.
Check that battery
terminal screws are
tightened.
Check that battery
terminals are
properly connected
to connectors.
FusionModule500 Smart Mini Data Center
User Manual 6 O&M
Issue 02 (2020-12-25) Copyright © Huawei Technologies Co., Ltd. 263

Table of Contents

Other manuals for Huawei FusionModule500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule500 and is the answer not in the manual?

Huawei FusionModule500 Specifications

General IconGeneral
BrandHuawei
ModelFusionModule500
CategoryStorage
LanguageEnglish

Related product manuals