Item Description Default Value Value Range
Output
voltage
level(V)
Species the system output
voltage level. This parameter
can be set only after the
inverter shuts down. After
you change the voltage level,
the upper limit of the bypass
voltage is restored to the
default value. (If the voltage
level is 380 V or 400 V, the
default upper limit is +15%.
If the voltage level is 415 V,
the default upper limit is
+10%.)
400 380, 400, 415
Output volt.
adjustment(V
)
The output voltage can be
slightly adjusted based on
the onsite power distribution
condition to ensure a
minimum dierence between
the output voltage and the
bypass voltage and to
facilitate uninterruptible
power supply when the UPS
transfers from normal mode
to bypass mode.
The default
value is 220.0,
230.0, and
240.0 when
the voltage
level is 380 V,
400 V, and 415
V respectively.
380 V: 209.0–
231.0
400 V: 218.5–
241.5
415 V: 228.0–
252.0
Output
frequency(Hz
)
Species the system output
frequency level.
50 Hz 50 Hz, 60 Hz
Current
equalization
detection
Monitors the current
dierences between racks or
modules. If this parameter is
set to Enable, the Mod. Cur.
Eql. Data can be viewed on
the running information
page.
Disable Disable,
Enable
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 4 LCD Interface
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 104