Indicator Color Status Description
Blinking
at long
interval
s
The bypass has no output (blinking at 0.2 Hz,
on for 2.5s and o for 2.5s).
Blinking
at short
interval
s
The bypass is not congured or the DSP
software is being upgraded (blinking at 4 Hz,
on for 0.125s and o for 0.125s).
O The bypass software is being upgraded.
Alarm
indicator
Yellow Steady
on
A minor alarm is generated for the bypass.
O There is no minor alarm for the bypass, or the
software is being upgraded.
Fault
indicator
Red Steady
on
A critical alarm is generated for the bypass.
O There is no critical alarm for the bypass, or
the software is being upgraded.
Functions
The bypass module supplies power in the following cases:
The UPS is set to ECO mode and the bypass voltage is within the
specied range.
The power module overload exceeds the time limit.
Both the active and standby ECMs are abnormal.
The system fails to run properly.
The power supply is switched to the bypass manually.
Specications
● Dimensions (H x W x D): 130 mm x 442 mm x 500 mm
● Weight: < 14 kg
● Rated output capacity: 200 kVA
2.3.4 Control Module
2.3.4.1 Overview
In a standard
conguration, the control module consists of two ECMs, one dry
contact card, and one monitoring interface card (from left to right). The four cards
are hot swappable. One subrack is reserved above the dry contact card. A
UPS5000-E-(30 kVA–180 kVA)