5.7 Testing Batteries
5.7.1 Lead-Acid Battery Test
5.7.1.1 Forced Equalized Charging Test
Context
NO TICE
Before a forced equalized charging test, ensure that:
The mains input is normal.
Batteries are properly connected.
Batteries are not in the equalized charging state.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 5 Operations
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 134