certain operations, and are able to take protective measures to minimize
the hazards on themselves and other people
Personnel who plan to install or maintain the equipment must receive
adequate training, be able to correctly perform all operations, and understand
all necessary safety precautions and local relevant standards.
Only
qualied professionals or trained personnel are allowed to install,
operate, and maintain the equipment.
Only
qualied professionals are allowed to remove safety facilities and inspect
the equipment.
Personnel who will perform special tasks such as electrical operations,
working at heights, and operations of special equipment should possess the
required local
qualications.
Only authorized professionals are allowed to replace the equipment or
components (including software).
Only personnel who need to work on the equipment are allowed to access
the equipment.
1.2 Equipment Safety
1.2.1 UPS Safety
General Requirements
NO TICE
The category 3 (C3) UPS is intended for commercial and industrial application in
the second class environment. Installation restrictions or additional measures may
be needed to prevent interference.
The UPS is used for commercial and industrial purposes only. It cannot be
used as a power supply for life support devices.
For power supply systems that are critical to signicant economic interests or
public order, such as the national computing center, emergency command
center, railway signal system and control center, civil aviation and air
trac
control center, airport command center, nancial clearing center, and
transaction center, the Tier 4 or 3 power architecture specied in TIA-942
must be used. That is, two power supplies must be used to supply power to
loads.
The UPS operating environment must meet the requirements for the climate
indicator, mechanically active substance indicator, and chemically active
substance indicator in ETSI EN 300 019-1 class 3.6.
The UPS must not be located in
non-conned environments near the ocean
(0–3.7 km) or indoor or semi-indoor environments where the temperature
and humidity are not controllable, such as simple equipment rooms, civil
houses, garages, corridors, and direct ventilation cabinets near the ocean; or
houses with only roofs, railway station platforms, gymnasiums, and
aquariums.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 1 Safety Information
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 4