EasyManua.ls Logo

Huawei UPS5000-E-30 kVA - Shallow Discharge Test

Huawei UPS5000-E-30 kVA
195 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Step 2 Tap Start next to Forced Equalized Charging to start a forced equalized charging
test.
Figure 5-8 Starting a forced equalized charging test
NO TE
The forced equalized charging test automatically stops in any of the following cases:
The test duration reaches the forced equalized charging protection time (12–24 h, 18 h
by default).
A battery overtemperature, overvoltage, or overcurrent alarm is generated.
A fault alarm is generated.
----End
5.7.1.2 Shallow Discharge Test
NO TICE
Before performing a shallow discharge test, ensure that:
If the battery has been replaced, choose System Info > Settings > Battery
Settings on the LCD and verify that the value of Installation time has been
changed based on the actual situation before testing the battery.
The UPS works in normal mode with a load rate
uctuation less than 10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent
alarm. No generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is
generated.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 5 Operations
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 135

Table of Contents

Related product manuals