Figure 4-38 PDU Param. screen 3
Figure 4-39 PDU Param. screen 4
Item Description Default Value Value Range
Br. cur. shock
protect (%)
Branch current surge
protection alarm threshold.
When the percentage of the
branch current to the rated
branch current exceeds the
threshold, an alarm is
generated.
300 150–500
X Harmonics,
Y Harmonics,
Z Harmonics
The system can display three
types of harmonics based on
the settings.
X harmonics: 5
Y harmonics: 7
Z harmonics:
11
2–63
Harmonic
alarm enable
Species whether to enable
harmonic alarms. If this
parameter is set to Enable,
an alarm (voltage/current
harmonic alarm) is
generated when the alarm
condition is met.
Disable Disable,
Enable
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 4 LCD Interface
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 114