EasyManua.ls Logo

Huawei UPS5000-E-30 kVA - Page 138

Huawei UPS5000-E-30 kVA
195 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Context
NO TICE
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter on the LCD.
On the main menu, choose Common Functions and tap Inv. ON.
NO TE
You can also tap System Info > Maintenance to shut down the inverter on the
Maintenance screen.
After the inverter shuts down, if the bypass is normal, the UPS works in bypass
mode; if the bypass is abnormal, the UPS supplies no power, and the loads power
o.
Figure 5-2 Normal bypass
NO TE
After you shut down the inverter, the Bypass mode alarm is displayed on the LCD.
UPS5000-E-(30 kVA–180 kVA)
User Manual (Integrated UPS) 5 Operations
Issue 02 (2022-12-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 130

Table of Contents

Related product manuals