NO TICE
Before a capacity test, ensure that:
The UPS is working in normal mode; oat charging or hibernation has lasted
for 2 hours after the state of charge (SOC) reaches 100%; and the load ratio
uctuation is less than 10%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent
alarm. No generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is
generated.
The SmartLi has generated no alarms related to lithium batteries.
Procedure
Step 1 On the home screen of the UPS LCD, choose System Info > Maintenance >
Battery Maint.
Step 2 Tap Start next to Capacity Test to start a capacity test.
Figure 5-12 Starting a capacity test
NO TE
The capacity test automatically stops in any of the following cases:
The minimum cell voltage reaches 2.65 V.
The load
uctuation exceeds 10%.
An alarm is generated.
The test is complete when the minimum cell voltage reaches 2.65 V. A maximum of recent
36 capacity test records can be saved.
----End