UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Copyright © Huawei Technologies Co., Ltd.
Make the red indicator on the iBAT start or stop blinking super fast.
Measure the battery internal resistance. If the condition for measuring
internal resistance is met (batteries are fully charged), you can tap Measure
to start measuring the internal resistance of the selected iBAT in an iBOX.
NOTE
The interval between two measurement operations must be greater than 10 minutes.
Bus capacitor life forecast
If the service life of a capacitor is about to end, that is, Module X bus capacitor life (y) is
less than 1.0, contact Huawei technical support to replace the power module.
Wizard Startup
The wizard startup can be used to test the bypass, mains inverter, inverter/bypass switch,
battery inverter, battery charging capability, battery switch tripping and so on.
Perform operations as prompted.
Before starting the wizard, ensure that: