Figure 5-21 Closing the maintenance bypass switch (UPS5000-E-300K-SMT, isolation 
protection) 
 
 
 
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed, Maint. breaker 
misoperation and Bypass mode alarms are displayed on the LCD. 
----End 
5.8 Transferring from Maintenance Bypass Mode to 
Normal Mode 
Context 
 
 
Before transferring the UPS from maintenance bypass mode to normal mode, ensure that the 
bypass input and output are normal. 
Procedure 
Step 1  Open the maintenance bypass switch. 
The Maint. breaker misoperation and Maint. Breaker closed alarms disappear from the 
alarm list. Check whether the UPS works in bypass mode by viewing the system running 
status diagram on the LCD or WebUI.