UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
Huawei technical support. 
Shallow discharge test 
(recommended) 
Conduct a shallow discharge 
test when the UPS is backed 
up to verify that the batteries 
can discharge normally. 
1.  If the batteries cannot 
discharge normally, locate 
the fault (for abnormal 
alarms, see the alarm list). 
2.  If the fault persists, contact 
Huawei technical support. 
 
6.2.4 Annual Maintenance 
Table 6-7 Annual maintenance 
When the UPS is backed up, 
discharge a battery to the 
undervoltage alarm threshold, to 
refresh the capacity of the battery. 
1.  Locate the cause when an 
exception is identified. 
2.  If the fault persists, contact 
Huawei technical support. 
Battery 
connection 
reliability 
1.  Each battery terminal is 
connected reliably. (When 
battery strings are powered 
off, check the reliability of 
each terminal in the order 
from positive terminals to 
negative terminals.) 
2.  The tightening torque of each 
battery screw meets the 
requirements of the battery 
manufacturer. (A torque 
wrench is used for checking 
the torque. After checking that 
the battery screws meet the 
requirements, mark the screws 
for later check.) 
1.  Rectify any abnormal 
connection. 
2.  If the fault persists, contact 
Huawei technical support.