EasyManuals Logo

Huawei UPS5000-E Series User Manual

Huawei UPS5000-E Series
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #252 background imageLoading...
Page #252 background image
UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
6 Routine Maintenance
Copyright © Huawei Technologies Co., Ltd.
242
Check Item
Expected Result
Troubleshooting
and noticeable sparks.
Cables and circuit breaker
through-current capacity
The circuit breakers and
cables meet load
requirements.
The actual cable
through-current capacity is
greater than the circuit
breaker specifications.
Replace the circuit
breaker.
Replace the cable.
To prevent system failures caused by the deterioration of some key UPS components, you are
advised to check the key components on a regular basis and replace them within the service
life.
Table 6-4 Service life parameters for replaceable components and recommended replacement
intervals
Key Component
Design Service Life
Recommended
Replacement Interval
Power module
15 years
10 years
Bypass module
15 years
10 years
Fan
15 years
10 years
LCD screen
10 years
8 years
6.2 Battery Maintenance
Before installing batteries, read through the battery user manuals and pay attention to safety
precautions and connection methods provided by battery manufacture.
When installing and maintaining batteries, pay attention to the following points:

Table of Contents

Other manuals for Huawei UPS5000-E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-E Series and is the answer not in the manual?

Huawei UPS5000-E Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-E Series
CategoryUPS
LanguageEnglish

Related product manuals