A critical alarm is generated for the bypass. 
There is no critical alarm for the bypass, or the FPGA 
software is being upgraded. 
 
Functions 
The bypass module supplies power in the following cases: 
If the UPS is set to ECO mode and the bypass voltage is within the specified range, the UPS 
works in bypass mode. 
If the power module overload times out, the UPS transfers to bypass mode. 
Both the active and standby ECMs are abnormal. 
The system fails to run properly and transfers to bypass mode. 
A manual operation is performed to transfer to bypass mode. 
Specifications 
 
Dimensions (H x W x D): 130 mm x 420 mm x 500 mm 
 
Weight 
−  200 kVA: 19 kg 
−  300 kVA: 23.8 kg 
2.3.4 Control Module 
2.3.4.1 Overview 
In a standard configuration, the control module consists of two ECMs, one dry contact card, 
and one monitoring interface card (from left to right). The four cards are hot swappable. One 
subrack is reserved above the dry contact card. A backfeed protection card or dry contact 
extended card can be inserted into this subrack. 
Figure 2-17 Signal panel on the control module 
 
(4) Ready switch 
on ECM 1 
(8) Ready switch 
on ECM 2