UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
8.7 Battery Specifications
12 V battery: 30–44 batteries (40 by default). 34 batteries, the
output power is derated to 90%. 32 and 30 batteries, the
output power is derated to 80%.
2 V battery: 180–264 batteries (240 by default). 204–214
batteries, the output power is derated to 90%. 180–204
batteries, the output power is derated to 80%.
The number of positive and negative battery strings must be
the same.
Intelligent battery management
In the case of a mains failure, batteries can start the UPS to power
loads.
Under rated conditions, the maximum charge power of a module
is 5 kW.
Battery string sharing is supported in a parallel system. No
battery string is shared by default.
Equalized voltage: 2.3–2.4 V/Cell, default: 2.35 V/Cell
(30–42 batteries)
Equalized voltage: 2.3–2.4 V/Cell, default: 2.35 V/Cell (44
batteries)
Float voltage: 2.23–2.3 V/Cell, default: 2.25 V/Cell (30–44
batteries)
8.8 Output Electrical Specifications
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
In normal mode, the mains frequency is synchronized with the
bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ±
0.05%).