UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
B Alarm List 
Alarm ID 
(Alarm 
ID-Cause 
ID) 
 
Cable 
connections are 
incorrect. 
 
The mains is not 
normal. 
 
The power 
module is faulty. 
 
The output or 
battery is 
incorrectly 
grounded. 
1.  Check whether cables to mains 
are disconnected, loose, or 
incorrectly connected. 
2.  If cable connections are 
correct, measure the mains 
voltage with a multimeter. If 
the mains voltage exceeds 280 
V, the mains input is not 
normal; if the mains voltage is 
less than 272 V, the sampling 
circuit of the power module is 
not normal. Replace the faulty 
module. 
3.  Check whether the output or 
battery is incorrectly 
grounded. 
 
Cable 
connections are 
incorrect. 
 
The mains is not 
normal. 
 
The mains input 
fuse for the 
power module is 
blown. 
1.  Check whether cables to mains 
are disconnected, loose, or 
incorrectly connected. 
2.  If cable connections are 
correct, measure the mains 
voltage with a multimeter. If 
the mains voltage is less than 
80 V, the mains voltage is not 
normal; if the mains voltage 
exceeds 88 V, the power 
module sampling circuit or 
fuse may not be working 
properly. Replace the faulty 
module.