UPS5000-E-(50 kVA-300 kVA) 
User Manual (50 kVA Power Modules) 
 
Copyright © Huawei Technologies Co., Ltd. 
 
7 Troubleshooting 
 
 
 
If the UPS is faulty, alarm information is displayed on the LCD. Clear critical alarms 
before powering on the UPS again. Otherwise, the fault scope expands or the UPS is 
damaged. 
 
Do not clear alarms by reseating modules. 
 
Remove a faulty module after it is confirmed that the module needs replacing. After 
removing the module, do not insert it into the UPS again. 
 
 
 
After a UPS finishes troubleshooting and is started, if the LCD continues displaying alarm 
information, choose System Info > Alarms > Clear Faults to clear the alarm and then 
start the inverter. 
 
When batteries reach EOD, the battery switch in the BCB box trips if the BCB box is 
configured. To restore battery discharge, close the battery switch in the BCB box (if any) 
first. 
 
To restore battery discharge after batteries reach EOD, use one of the following methods: 1. 
Switch to another battery string. Ensure that each battery has a voltage greater than the 
EOD voltage and 11.3 V/cell. 2. Restore the mains power supply to start the inverter. 
Close the battery switch and charge batteries until each battery has a voltage greater than 
the EOD voltage and 11.3 V/cell. 
For details about how to rectify common faults, see Table 7-1. If any unmentioned faults 
occur, see the alarm list chapter, or contact Huawei technical support. 
Table 7-1 Troubleshooting 
The rectifier is not 
working, and the bus 
voltage is not boosted. 
The mains voltage 
exceeds the upper 
threshold 280 V or is 
less than the lower 
Check whether the 
mains voltage exceeds 
the threshold. If yes, 
contact the electric