UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
181
Item
Description
Default Value
Value Range
recovery time.
Capacitor
failure
detection
If Capacitor failure detection is
set to Enable, the power module
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Disable
Disable, Enable
Table 4-15 Bypass settings
Item
Description
Default Value
Value Range
BPM mode
upon BPM
overtemp.
Specifies whether to start bypass
mode when overtemperature
occurs.
Enable
Disable, Enable
Lightload
BPM cur. eql.
detect
Enable or disable the light load
bypass current imbalance alarm.
If this parameter is set to Enable,
the load is light (less than 30%
load), and the load rate of a
certain rack is less than 10%, the
system will generate a bypass
current imbalance alarm and
cannot enter the ECO mode. If
this parameter is set to Disable,
the preceding detection is not
performed. Whether the bypass
current is imbalanced does not
affect the ECO bypass mode.
Enable
Disable, Enable
Battery
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following: