UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Copyright © Huawei Technologies Co., Ltd.
183
Item
Description
Default Value
Value Range
charging
protection
interval (d)
charging protection interval.
After equalized charging is
complete, scheduled equalized
charging starts when the
non-equalized charging time
exceeds Scheduled equalized
charging interval.
Forced
equalized
charging
protection
time (h)
When batteries are continuously
under float charging or
hibernation, enable forced
equalized charging. When the
forced equalized charging time
reaches the value of this
parameter, batteries
automatically transfer to float
charging mode.
18
1224
Max. batt. dis.
time (h)
Set the maximum battery
discharge time. When the
discharge time reaches this value,
the UPS powers off. The battery
discharge time can be set only to
0 hours or a value only in the
range of 1648 hours. If the time
is set to 0 hours, battery
discharge protection is not
implemented.
24
048
Undertemp.
alarm thresh.
C)
Battery temperatures can be
monitored in a timely manner. If
a battery overtemperature alarm
is detected, the charging current
limit decreases to 0.03 CA.
Battery charging stops if a
battery overtemperature
protection alarm (when the
temperature reaches the high
temperature threshold plus 3°C)
is generated.
C
20°C to +5°C
Overtemp.
alarm thresh.
C)
50°C
35°C to 55°C
Single batt.
float chg.
voltage
deviation
alarm thres.
(%)
Single batt. float chg. voltage
deviation alarm thres. (%) and
Single batt. dis. voltage
deviation alarm thres. (%) are
used to check whether the cells in
each battery string have the same
charge voltage and discharge
voltage. When a value exceeds
the specified range, an alarm is
generated.
The calculation formula is
(Charge/Discharge voltage
Average voltage)/Average
10
530
Single batt.
dis. voltage
deviation
alarm thres.
(%)
20
1030