UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Copyright © Huawei Technologies Co., Ltd.
221
Figure 5-2 Setting the Internet options
Step 3 In the address box of the browser, enter https://UPS IP address.
Step 4 Enter the correct user name and password and click Login.
Step 5 On the home page of the WebUI, choose Monitoring > UPS System > Running Control,
click Inv. ON, and confirm the operation to start the inverter.
Figure 5-3 Starting the inverter
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
----End
Starting the UPS on the Old WebUI
Step 1 Open a browser (Internet Explorer 11 for example) and choose Tools > Internet Options.
Step 2 Click the Advanced tab, check that Use TLS 1.0 and Use TLS 1.1 are selected, and then
click OK.

Table of Contents

Other manuals for Huawei UPS5000-E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-E Series and is the answer not in the manual?

Huawei UPS5000-E Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-E Series
CategoryUPS
LanguageEnglish

Related product manuals