UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Copyright © Huawei Technologies Co., Ltd.
239
Figure 5-25 Running Parameter
Click Submit after setting parameters on the WebUI.
Old Web
1. On the WebUI, choose Monitoring > Param. Settings > System Settings and set Paral.
sys. hibernate to Enable.
2. Set the module cycle hibernation period to an integer ranging from 1 to 100. The default
value is 30.
Figure 5-26 System settings
Click Submit after setting parameters on the WebUI.