UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
B Alarm List
Copyright © Huawei Technologies Co., Ltd.
263
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
0583-1
Inter-rack par. cable
abnormal
Critical
The inter-rack
parallel system
CAN bus is
disconnected or
short-circuited.
Only one rack
works in a
parallel system.
An ECM is
faulty.
1. Check the inter-rack parallel
system CAN bus.
2. Rectify the disconnection or
short-circuit fault.
3. Replace the ECM.
0583-4
The inter-rack
industrial frequency
synchronization
cable is broken.
Replace the inter-rack parallel
cable.
0583-5
The inter-rack
carrier
synchronization
cable is broken.
0583-6
The intra-rack
INVBYP cable is
broken.
The parallel
CAN bus is
broken.
0584-2
Inter-rack par. cable
alarm
Minor
The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel
cable.
0584-4
The inter-rack
industrial frequency
synchronization
cable is broken.
0085-1
EPO
Critical
The EPO button is
pressed.
Restore the EPO button status.
Start the UPS after the alarm is
cleared.
0086-1
Max. number of
BPM transfers
Minor
The system
frequently transfers
to bypass mode due
to overload timeout
or load impact.
Check the load.
0087-1
System
transfer-to-bypass
Warning
The neighboring
UPS is not normal,
and transfers to
bypass mode.
Check the reason why the
neighboring UPS transfers to
bypass mode.

Table of Contents

Other manuals for Huawei UPS5000-E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS5000-E Series and is the answer not in the manual?

Huawei UPS5000-E Series Specifications

General IconGeneral
BrandHuawei
ModelUPS5000-E Series
CategoryUPS
LanguageEnglish

Related product manuals