UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Copyright © Huawei Technologies Co., Ltd.
53
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM
/SMT
50 kVA
100 kVA
150 kVA
200 kVA
250 kVA
300 kVA
Mains
input
Mains input current (A)
89
178
267
355
444
533
Recommended
cross-sectional
area (mm
2
)
L1
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
L2
L3
N
PE
25
35
70
95
120
150
Bypass
input
Bypass input current
(A)
76
152
228
304
380
456
Recommended
cross-sectional
area (mm
2
)
L1
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
L2
L3
N
PE
25
35
70
95
120
150
Output
Output current (A)
76
152
228
304
380
456
Recommended
cross-sectional
area (mm
2
)
U
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
V
W
N
PE
25
35
70
95
120
150
Battery
input
Battery nominal
discharge current (A)
110
219
329
439
548
658
Battery maximum
discharge current (A)
131
263
394
525
657
788
Recommended
cross-sectional
area (mm
2
)
+
3 x 35
3 x 95
2 x (3 x
95)
2 x (3 x
120)
2 x (3 x
150)
2 x (3 x
185)
N
-
PE
35
50
95
120
150
185
When selecting, connecting, and routing power cables, follow local safety regulations